Backflow assembly test: 8719 Hickory Trl
ApprovedFiled Dec 10, 2025 by Reese Ellery, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 10, 2025
- Assembly type
- PVB
- Serial number
- Z954087
- Size
- 1
- Test gauge serial
- G-2746
- Gauge calibration date
- Jun 3, 2025
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Ellery, current on the service date
- All required fields present
- Address matches parcel 045-19-01285
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8719 Hickory Trl
Owner: Emerson Wexler
Parcel 045-19-01285