Backflow assembly test: 3909 Spring Branch Dr

Approved

Filed Nov 8, 2026 by Cameron Whitcomb, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 8, 2026
Assembly type
RP
Serial number
B662180
Size
1
Test gauge serial
G-7011
Gauge calibration date
Jan 26, 2026
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
2.8 psid
Relief valve opened at
3.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 045-10-01103
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3909 Spring Branch Dr
Owner: Blake Ellery
Parcel 045-10-01103