Backflow assembly test: 4783 Spring Branch Ct
ApprovedFiled Aug 26, 2025 by Reese Ellery, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 26, 2025
- Assembly type
- RP
- Serial number
- W964406
- Size
- 3/4
- Test gauge serial
- G-4847
- Gauge calibration date
- Sep 17, 2024
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 1.7 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Ellery, current on the service date
- All required fields present
- Address matches parcel 045-94-01224
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4783 Spring Branch Ct
Owner: Drew Fairley
Parcel 045-94-01224