Backflow assembly test: 3278 Old Church Ln

Approved

Filed Feb 26, 2026 by Reese Ellery, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 26, 2026
Assembly type
DC
Serial number
A189805
Size
1
Test gauge serial
G-9257
Gauge calibration date
Dec 6, 2025
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Ellery, current on the service date
  • All required fields present
  • Address matches parcel 045-99-01054
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3278 Old Church Ln
Owner: Jamie Marsh
Parcel 045-99-01054