Backflow assembly test: 1075 Ridgeview Rd

Approved

Filed Aug 15, 2025 by Drew Vance, Clearwater Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 15, 2025
Assembly type
RP
Serial number
W709813
Size
3/4
Test gauge serial
G-1732
Gauge calibration date
Jun 12, 2025
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Vance, current on the service date
  • All required fields present
  • Address matches parcel 045-49-01239
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.