Back to the backflow review queue

Backflow assembly test: Blue Heron Market

Approved

Filed Jan 13, 2025 by Morgan Pruitt, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 13, 2025
Assembly type
RP
Serial number
W959773
Size
1
Test gauge serial
G-7099
Gauge calibration date
Jun 30, 2024
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 131-35-01219
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9534 Mill Creek Rd
Owner: Benton Holdings LLC
Parcel 131-35-01219