Back to the backflow review queue

Backflow assembly test: Hilltop Elementary School

Approved

Filed May 18, 2026 by Emerson Benton, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
May 18, 2026
Assembly type
RP
Serial number
A800850
Size
1 1/2
Test gauge serial
G-1840
Gauge calibration date
Sep 17, 2025
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Benton, current on the service date
  • All required fields present
  • Address matches parcel 131-25-01139
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4992 Stone Gate Rd
Owner: Hollins Holdings LLC