Back to the backflow review queue

Backflow assembly test: 4763 Old Church Way

Approved

Filed Apr 23, 2026 by Hayden Okafor, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Apr 23, 2026
Assembly type
RP
Serial number
A302852
Size
1
Test gauge serial
G-4379
Gauge calibration date
Mar 14, 2026
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Okafor, current on the service date
  • All required fields present
  • Address matches parcel 131-38-01237
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4763 Old Church Way
Owner: Hayden Ellery
Parcel 131-38-01237