Backflow assembly test: 6018 Mill Creek Ct

Approved

Filed Oct 10, 2026 by Hayden Pruitt, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 10, 2026
Assembly type
RP
Serial number
Z496493
Size
1
Test gauge serial
G-4503
Gauge calibration date
Jul 1, 2026
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 131-97-01257
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6018 Mill Creek Ct
Owner: Riley Hollins
Parcel 131-97-01257