Back to the backflow review queue

Backflow assembly test: 932 Ridgeview Ln

Approved

Filed Mar 3, 2025 by Hayden Okafor, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Mar 3, 2025
Assembly type
RP
Serial number
W242555
Size
3/4
Test gauge serial
G-3412
Gauge calibration date
Oct 14, 2024
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Okafor, current on the service date
  • All required fields present
  • Address matches parcel 131-57-01181
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

932 Ridgeview Ln
Owner: Morgan Ramirez
Parcel 131-57-01181