Back to the backflow review queue

Backflow assembly test: 4280 Hickory Way

Approved

Filed Mar 30, 2025 by Hayden Okafor, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Mar 30, 2025
Assembly type
RP
Serial number
B353690
Size
1
Test gauge serial
G-3270
Gauge calibration date
Jul 6, 2024
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Okafor, current on the service date
  • All required fields present
  • Address matches parcel 131-34-01087
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4280 Hickory Way
Owner: Parker Nguyen
Parcel 131-34-01087