Backflow assembly test: Hilltop Medical Offices

Approved

Filed May 28, 2026 by Hayden Okafor, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
May 28, 2026
Assembly type
RP
Serial number
W966131
Size
4
Test gauge serial
G-7449
Gauge calibration date
Mar 9, 2025
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Okafor, current on the service date
  • All required fields present
  • Address matches parcel 131-52-01244
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.