Back to the backflow review queue

Backflow assembly test: 7579 Turkey Hill Ln

Approved

Filed Jul 2, 2023 by Hayden Okafor, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Jul 2, 2023
Assembly type
RP
Serial number
B598327
Size
3/4
Test gauge serial
G-5034
Gauge calibration date
Sep 29, 2022
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Okafor, current on the service date
  • All required fields present
  • Address matches parcel 131-90-01137
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7579 Turkey Hill Ln
Owner: Avery Okafor
Parcel 131-90-01137