Backflow assembly test: 7579 Turkey Hill Ln
ApprovedFiled Aug 8, 2024 by Logan Okafor, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 8, 2024
- Assembly type
- RP
- Serial number
- B598327
- Size
- 3/4
- Test gauge serial
- G-2906
- Gauge calibration date
- Feb 24, 2024
- Check valve 1
- 3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Okafor, current on the service date
- All required fields present
- Address matches parcel 131-90-01137
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.