Back to the backflow review queue

Backflow assembly test: Station Taqueria

Approved

Filed May 2, 2025 by Logan Okafor, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 2, 2025
Assembly type
RP
Serial number
K234921
Size
1
Test gauge serial
G-5787
Gauge calibration date
Mar 22, 2025
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Okafor, current on the service date
  • All required fields present
  • Address matches parcel 131-99-01031
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3174 Laurel Way
Owner: Vance Holdings LLC
Parcel 131-99-01031