Backflow assembly test: 7039 Old Church Rd

Approved

Filed Jul 4, 2025 by Parker Ashby, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 4, 2025
Assembly type
RP
Serial number
K453623
Size
3/4
Test gauge serial
G-3454
Gauge calibration date
Sep 30, 2024
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 131-24-01196
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7039 Old Church Rd
Owner: Alex Brandt
Parcel 131-24-01196