Backflow assembly test: 5719 Sycamore Dr

Approved

Filed May 29, 2023 by Parker Ashby, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 29, 2023
Assembly type
RP
Serial number
W100095
Size
1
Test gauge serial
G-7949
Gauge calibration date
Oct 11, 2022
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 131-79-01299
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.