Backflow assembly test: Main Street Bakery
ApprovedFiled Aug 3, 2025 by Jamie Ashby, Summit Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 3, 2025
- Assembly type
- RP
- Serial number
- A678381
- Size
- 1
- Test gauge serial
- G-3585
- Gauge calibration date
- Nov 10, 2024
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jamie Ashby, current on the service date
- All required fields present
- Address matches parcel 143-97-01319
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
809 Meadow Lark Ln
Owner: Vance Holdings LLC
Parcel 143-97-01319