Backflow assembly test: 9332 Orchard Rd
ApprovedFiled May 15, 2024 by Jamie Ashby, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- May 15, 2024
- Assembly type
- RP
- Serial number
- K676027
- Size
- 3/4
- Test gauge serial
- G-4315
- Gauge calibration date
- Apr 3, 2023
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2 psid
- Relief valve opened at
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jamie Ashby, current on the service date
- All required fields present
- Address matches parcel 143-44-01158
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
9332 Orchard Rd
Owner: Alex Calloway
Parcel 143-44-01158