Backflow assembly test: 9477 Cedar Hollow Ln
ApprovedFiled Jun 19, 2025 by Jamie Ashby, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 19, 2025
- Assembly type
- RP
- Serial number
- W647640
- Size
- 1
- Test gauge serial
- G-1018
- Gauge calibration date
- May 15, 2025
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jamie Ashby, current on the service date
- All required fields present
- Address matches parcel 143-58-01105
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.