Back to the backflow review queue
Backflow assembly test: Golden Taqueria
ApprovedFiled Jul 30, 2025 by Blake Wexler, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 30, 2025
- Assembly type
- RP
- Serial number
- Z264814
- Size
- 1 1/2
- Test gauge serial
- G-4835
- Gauge calibration date
- Dec 6, 2024
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes