Back to the backflow review queue

Backflow assembly test: 9396 Spring Branch Trl

Approved

Filed Jun 11, 2026 by Taylor Pruitt, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jun 11, 2026
Assembly type
RP
Serial number
A725238
Size
3/4
Test gauge serial
G-6342
Gauge calibration date
Apr 18, 2026
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 143-64-01326
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9396 Spring Branch Trl
Owner: Drew Harlow
Parcel 143-64-01326