Back to the backflow review queue
Backflow assembly test: Station Taqueria
ApprovedFiled Apr 24, 2026 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Apr 24, 2026
- Assembly type
- RP
- Serial number
- K740813
- Size
- 2
- Test gauge serial
- G-2280
- Gauge calibration date
- Jan 16, 2026
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Fairley, current on the service date
- All required fields present
- Address matches parcel 143-38-01222
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3296 Orchard Dr
Owner: Calloway Holdings LLC
Parcel 143-38-01222