Backflow assembly test: Station Taqueria

Approved

Filed Apr 24, 2026 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Apr 24, 2026
Assembly type
RP
Serial number
K740813
Size
2
Test gauge serial
G-2280
Gauge calibration date
Jan 16, 2026
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 143-38-01222
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.