Backflow assembly test: 2426 Old Church Way

Approved

Filed Jul 1, 2024 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Jul 1, 2024
Assembly type
RP
Serial number
K164587
Size
1
Test gauge serial
G-7384
Gauge calibration date
Nov 4, 2023
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 143-62-01249
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.