Backflow assembly test: 8063 Stone Gate Rd
ApprovedFiled Jun 1, 2025 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 1, 2025
- Assembly type
- RP
- Serial number
- Z870736
- Size
- 3/4
- Test gauge serial
- G-6032
- Gauge calibration date
- Dec 3, 2024
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Fairley, current on the service date
- All required fields present
- Address matches parcel 143-66-01230
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8063 Stone Gate Rd
Owner: Quinn Brandt
Parcel 143-66-01230