Backflow assembly test: 7096 Orchard Trl

Approved

Filed Jul 31, 2026 by Alex Benton, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 31, 2026
Assembly type
DC
Serial number
A475456
Size
1
Test gauge serial
G-3693
Gauge calibration date
Oct 15, 2025
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 001-94-01014
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.