Backflow assembly test: Blue Heron Diner

Approved

Filed Oct 20, 2025 by Rowan Okafor, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Oct 20, 2025
Assembly type
RP
Serial number
A364921
Size
1
Test gauge serial
G-8297
Gauge calibration date
Jul 7, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Okafor, current on the service date
  • All required fields present
  • Address matches parcel 001-25-01197
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.