Backflow assembly test: Main Street Grill

Approved

Filed Dec 9, 2025 by Alex Benton, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 9, 2025
Assembly type
RP
Serial number
B571957
Size
1
Test gauge serial
G-5257
Gauge calibration date
May 14, 2025
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 001-45-01109
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.