Backflow assembly test: Crossroads Bakery
ApprovedFiled Nov 5, 2025 by Rowan Okafor, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 5, 2025
- Assembly type
- RP
- Serial number
- K639454
- Size
- 4
- Test gauge serial
- G-3476
- Gauge calibration date
- Apr 22, 2025
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Okafor, current on the service date
- All required fields present
- Address matches parcel 001-20-01211
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.