Backflow assembly test: 2402 Mill Creek Dr
ApprovedFiled Mar 29, 2023 by Avery Ellery, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Mar 29, 2023
- Assembly type
- RP
- Serial number
- Z877369
- Size
- 1
- Test gauge serial
- G-3167
- Gauge calibration date
- Mar 26, 2022
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 1.7 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ellery, current on the service date
- All required fields present
- Address matches parcel 001-42-01076
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.