Back to the backflow review queue

Backflow assembly test: Corner Elementary School

Approved

Filed Sep 5, 2025 by Rowan Okafor, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Sep 5, 2025
Assembly type
RP
Serial number
K614381
Size
4
Test gauge serial
G-4329
Gauge calibration date
Jan 20, 2025
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Okafor, current on the service date
  • All required fields present
  • Address matches parcel 001-18-01245
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7360 Laurel Trl
Owner: Lindqvist Holdings LLC
Parcel 001-18-01245