Backflow assembly test: Hilltop Apartments
ApprovedFiled Aug 6, 2025 by Quinn Nguyen, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 6, 2025
- Assembly type
- RP
- Serial number
- B266862
- Size
- 1 1/2
- Test gauge serial
- G-1510
- Gauge calibration date
- Jan 2, 2025
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Nguyen, current on the service date
- All required fields present
- Address matches parcel 001-62-01285
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7578 Quarry Dr
Owner: Nguyen Holdings LLC
Parcel 001-62-01285