Back to the backflow review queue

Backflow assembly test: 9123 Meadow Lark Trl

Filed Nov 20, 2026 by Riley Danner, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Nov 20, 2026
Assembly type
RP
Serial number
W211848
Size
1
Test gauge serial
G-1426
Gauge calibration date
Sep 26, 2026
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Danner, current on the service date
  • All required fields present
  • Address matches parcel 001-15-01059
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

9123 Meadow Lark Trl
Owner: Emerson Wexler
Parcel 001-15-01059