Back to the backflow review queue

Backflow assembly test: 2810 Cedar Hollow Dr

Approved

Filed Jun 26, 2025 by Rowan Okafor, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 26, 2025
Assembly type
PVB
Serial number
Z945940
Size
3/4
Test gauge serial
G-4962
Gauge calibration date
Sep 27, 2024
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Okafor, current on the service date
  • All required fields present
  • Address matches parcel 001-91-01272
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2810 Cedar Hollow Dr
Owner: Hayden Okafor
Parcel 001-91-01272