Back to the backflow review queue

Backflow assembly test: Riverside Market

Approved

Filed Aug 7, 2025 by Parker Kessler, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 7, 2025
Assembly type
DC
Serial number
W186508
Size
1 1/2
Test gauge serial
G-3174
Gauge calibration date
Feb 24, 2025
Check valve 1
0.3 psid
Check valve 1 closed tight
No
Check valve 2
2.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Kessler, current on the service date
  • All required fields present
  • Address matches parcel 001-97-01042
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6072 Cedar Hollow Rd
Owner: Danner Holdings LLC
Parcel 001-97-01042