Backflow assembly test: 8969 Mill Creek Trl

Approved

Filed Jan 3, 2024 by Quinn Nguyen, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 3, 2024
Assembly type
DC
Serial number
W165081
Size
3/4
Test gauge serial
G-5071
Gauge calibration date
Aug 13, 2023
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 001-45-01345
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8969 Mill Creek Trl
Owner: Jordan Marsh
Parcel 001-45-01345