Back to the backflow review queue

Backflow assembly test: 6375 Spring Branch Ct

Approved

Filed Dec 16, 2025 by Riley Danner, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 16, 2025
Assembly type
RP
Serial number
Z767820
Size
3/4
Test gauge serial
G-8595
Gauge calibration date
Dec 23, 2024
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
2.6 psid
Relief valve opened at
2.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Danner, current on the service date
  • All required fields present
  • Address matches parcel 001-20-01261
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6375 Spring Branch Ct
Owner: Sam Brandt
Parcel 001-20-01261