Back to the backflow review queue
Backflow assembly test: 707 Orchard Ct
ApprovedFiled Dec 11, 2023 by Rowan Okafor, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 11, 2023
- Assembly type
- RP
- Serial number
- Z161731
- Size
- 3/4
- Test gauge serial
- G-6466
- Gauge calibration date
- Apr 17, 2023
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Okafor, current on the service date
- All required fields present
- Address matches parcel 001-56-01257
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
707 Orchard Ct
Owner: Cameron Danner
Parcel 001-56-01257