Backflow assembly test: 2792 Pine Knoll Way

Approved

Filed Aug 10, 2026 by Sam Brandt, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Aug 10, 2026
Assembly type
RP
Serial number
K198876
Size
1
Test gauge serial
G-7910
Gauge calibration date
Jun 7, 2025
Check valve 1
0.3 psid
Check valve 1 closed tight
No
Check valve 2
2.6 psid
Relief valve opened at
3.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 001-94-01224
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2792 Pine Knoll Way
Owner: Alex Danner
Parcel 001-94-01224