Back to the backflow review queue

Backflow assembly test: Crossroads Elementary School

Approved

Filed Oct 6, 2026 by Sam Brandt, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 6, 2026
Assembly type
RP
Serial number
W477285
Size
4
Test gauge serial
G-2809
Gauge calibration date
Mar 5, 2026
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 001-14-01037
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6707 Quarry Rd
Owner: Ashby Holdings LLC
Parcel 001-14-01037