Backflow assembly test: 9389 Cedar Hollow Trl

Approved

Filed Oct 16, 2026 by Parker Kessler, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Oct 16, 2026
Assembly type
RP
Serial number
K998091
Size
1
Test gauge serial
G-4177
Gauge calibration date
Apr 3, 2026
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Kessler, current on the service date
  • All required fields present
  • Address matches parcel 001-98-01215
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9389 Cedar Hollow Trl
Owner: Jordan Whitcomb
Parcel 001-98-01215