Backflow assembly test: 9716 Hickory Ln
ApprovedFiled May 18, 2025 by Sam Brandt, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- May 18, 2025
- Assembly type
- RP
- Serial number
- W199567
- Size
- 1
- Test gauge serial
- G-4302
- Gauge calibration date
- Sep 14, 2024
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Brandt, current on the service date
- All required fields present
- Address matches parcel 001-44-01189
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
9716 Hickory Ln
Owner: Morgan Whitcomb
Parcel 001-44-01189