Backflow assembly test: Blue Heron Diner

Approved

Filed Sep 18, 2025 by Riley Danner, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Sep 18, 2025
Assembly type
RP
Serial number
W949446
Size
1 1/2
Test gauge serial
G-5685
Gauge calibration date
Aug 17, 2025
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Danner, current on the service date
  • All required fields present
  • Address matches parcel 001-65-01239
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

186 Laurel Way
Owner: Ashby Holdings LLC
Parcel 001-65-01239