Backflow assembly test: 6425 Stone Gate Ct

Approved

Filed Sep 25, 2026 by Logan Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Sep 25, 2026
Assembly type
RP
Serial number
A571566
Size
3/4
Test gauge serial
G-9219
Gauge calibration date
Jun 22, 2026
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Kessler, current on the service date
  • All required fields present
  • Address matches parcel 009-94-01005
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6425 Stone Gate Ct
Owner: Emerson Fairley
Parcel 009-94-01005