Backflow assembly test: 8488 Fox Run Rd

Approved

Filed Aug 30, 2025 by Logan Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Aug 30, 2025
Assembly type
RP
Serial number
A573420
Size
1
Test gauge serial
G-1509
Gauge calibration date
Dec 14, 2024
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Kessler, current on the service date
  • All required fields present
  • Address matches parcel 009-93-01243
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8488 Fox Run Rd
Owner: Jamie Wexler
Parcel 009-93-01243