Backflow assembly test: 6229 Pine Knoll Ct

Approved

Filed Jan 18, 2026 by Reese Benton, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jan 18, 2026
Assembly type
RP
Serial number
Z952669
Size
1
Test gauge serial
G-8739
Gauge calibration date
Sep 27, 2025
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Benton, current on the service date
  • All required fields present
  • Address matches parcel 009-94-01302
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6229 Pine Knoll Ct
Owner: Jamie Kessler
Parcel 009-94-01302