Backflow assembly test: 5309 Cedar Hollow Ln

Approved

Filed May 18, 2025 by Sam Ellery, Summit Backflow Testing. Filed from a phone.

Report

Date of service
May 18, 2025
Assembly type
PVB
Serial number
K911058
Size
3/4
Test gauge serial
G-7607
Gauge calibration date
Feb 11, 2025
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Ellery, current on the service date
  • All required fields present
  • Address matches parcel 009-66-01281
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5309 Cedar Hollow Ln
Owner: Blake Stroud
Parcel 009-66-01281