Back to the backflow review queue

Backflow assembly test: 4049 Old Church Rd

Approved

Filed Nov 7, 2026 by Blake Ellery, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Nov 7, 2026
Assembly type
RP
Serial number
K776572
Size
1
Test gauge serial
G-6494
Gauge calibration date
Jul 5, 2026
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Ellery, current on the service date
  • All required fields present
  • Address matches parcel 009-14-01337
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4049 Old Church Rd
Owner: Sam Hollins
Parcel 009-14-01337