ApprovedFiled May 23, 2024 by Blake Ellery, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- May 23, 2024
- Assembly type
- RP
- Serial number
- K673080
- Size
- 1 1/2
- Test gauge serial
- G-6555
- Gauge calibration date
- Jan 14, 2024
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Ellery, current on the service date
- All required fields present
- Address matches parcel 009-81-01163
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.