Backflow assembly test: Riverside Market
ApprovedFiled Jan 9, 2026 by Emerson Marsh, Summit Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jan 9, 2026
- Assembly type
- RP
- Serial number
- A915263
- Size
- 1
- Test gauge serial
- G-5036
- Gauge calibration date
- Aug 18, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Marsh, current on the service date
- All required fields present
- Address matches parcel 009-23-01236
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.